Hybrid / Polymer Bushing for Pole Transformer
PRODUCTS

APPLICATION
Protects high voltage and low voltage side terminal of pole transformer
CHARACTERISTIC
- Excellent impact resistance
- Prevent oil leakage
- High water repellency
- Light weight & Easy installation
SPECIFICATION
SpecificationsUnitsHighLowRated currentA40500Material–Porcelain / SiliconePorcelain-FRP / SiliconePower frequency withstand voltage (dry)kV4215Power frequency withstand voltage (wet)kV3615Lightning impulse withstand voltage
(1.2 × 50μs)kV125–Leakage distancemm770 ±40–